Using the Pt-MU measuring transducer, the signal of a Pt100 is converted into a standard signal proportional to the temperature. For example, the measuring transducer can be connected to the Pt100 connections in the ZT-F2.1 transformer temperature sensor or the combi well. It prepares the output signals of these devices for further processes in the computer or electrical/electronic display. The Pt-MU is used anywhere where measured values need to be transmitted over large distances or interference fields are located in the transmission path.
Product Information
Input variable | Resistance PT100 |
Rated values | Any temperature range between -200 - 850 °C (minimum span 40 K) |
Outputs | 0-20 mA/0-500 Ohm load and 0-10 V max. 10 mA load as well as 4-20 mA/0-500 Ohm load and 2-10 V max. 10 mA load |
Accuracy | +/- 0,5% of full scale |
Response time | < 300 ms (with frequency module < 400 ms) |
Operation temperature | -15 to +20 to +30 to +55 °C |
Storage temperature | -25 - 85 °C |
Temperature influence | <0,2 % at 10 K |
Ambient conditions | Stationary application, weather protected, rel. air humidity 5 - 95 %, no condensation, altitude up to 2000 m, water, rain, snow or hail excluded |
Select language
Please make a selection to display suitable downloads
Technical Data
Input variable | Resistance PT100 |
Rated values | Any temperature range between -200 - 850 °C (minimum span 40 K) |
Outputs | 0-20 mA/0-500 Ohm load and 0-10 V max. 10 mA load as well as 4-20 mA/0-500 Ohm load and 2-10 V max. 10 mA load |
Accuracy | +/- 0,5% of full scale |
Response time | < 300 ms (with frequency module < 400 ms) |
Operation temperature | -15 to +20 to +30 to +55 °C |
Storage temperature | -25 - 85 °C |
Temperature influence | <0,2 % at 10 K |
Ambient conditions | Stationary application, weather protected, rel. air humidity 5 - 95 %, no condensation, altitude up to 2000 m, water, rain, snow or hail excluded |