CAPT® 040 +

De-energized tap changer for a rated current of up to 2700 A

The CAPT® 040+ DETC (de-energized tap-changer) series combines high performance, robust reliability,  and compliance with the latest product standards. Its optimized mechanical architecture and innovative contact design support high current ratings and flexible applications without compromising durability. The design enables vertical and horizontal installation, allowing multiple types of mounting layouts. A gear transmission mechanism ensures smooth motion and precise and distinct positioning. 

Optional equipotential rings and pressboard shields support optimized electric field distribution and provide greater flexibility when integrating the DETC in close proximity to other active transformer components. The optional DETC CONTROL motor drive unit enables remote operation and is engineered for long-term, maintenance-free service. Backward-compatible with the CAPT® 040 series, CAPT® 040+ is ideal for modern electrical equipment requiring higher current capacity and reliable operation.

Sus ventajas de un vistazo

  1. Specific design to withstand high current ratings, up to 2700 A

  2. Highly customizable design, adaptable to transformer’s needs

  3. Direct and remote control available

  4. Maintenance-free throughout the entire service life of the transformer

  5. Full compliance with IEC 60214-1 and IEEE C57.131

  6. Compatible with mineral oils and alternative insulation liquids

Mostrar todo

Información sobre el producto

Maximum voltage for equipment 26 kV / 36 kV / 52 kV / 73 kV
Max. rated current 1000 A / 1600 A
2700 A with parallel contacts and non-enforced current splitting (in accordance with IEC 60214-2)
Number of stages 1-6
Number of operating positions 2 … 15
Number of decks per column 1-4
Number of columns 1-3
Rated frequency 50 Hz / 60 Hz
Drive Manual drive (070-1.xxx) / Motor drive (DETC CONTROL)
Insulating fluid Mineral oils in accordance with IEC 60296
Compatible with synthetic and natural ester liquids
Temperature of the insulating fluid during operation Standard: -40 °C to +115 °C
Optional: -60 °C or +155 °C
Type tests In accordance with IEC 60214-1:2014 and IEEE C57.131-2024

  • Full compliance with IEC 60214-1 (tap changers performance requirements and test methods) 
  • Full compliance with IEEE C57.131 (standard performance requirements and test methods for tap changers) 
  • Full compliance with REACH 
  • PFAS free
Maximum voltage for equipment 26 kV / 36 kV / 52 kV / 73 kV
Max. rated current 1000 A / 1600 A
2700 A with parallel contacts and non-enforced current splitting (in accordance with IEC 60214-2)
Number of stages 1-6
Number of operating positions 2 … 15
Number of decks per column 1-4
Number of columns 1-3
Rated frequency 50 Hz / 60 Hz
Drive Manual drive (070-1.xxx) / Motor drive (DETC CONTROL)
Insulating fluid Mineral oils in accordance with IEC 60296
Compatible with synthetic and natural ester liquids
Temperature of the insulating fluid during operation Standard: -40 °C to +115 °C
Optional: -60 °C or +155 °C
Type tests In accordance with IEC 60214-1:2014 and IEEE C57.131-2024
  • Full compliance with IEC 60214-1 (tap changers performance requirements and test methods) 
  • Full compliance with IEEE C57.131 (standard performance requirements and test methods for tap changers) 
  • Full compliance with REACH 
  • PFAS free

„More current. Less space. With CAPT® 040+, customers no longer have to choose between compactness and performance.“

Petra Wiethoff | Product Manager

United States of America


In order to offer you the best possible service, we would like to refer you directly to the right contact person. Please click on the following link.

US contacts

United States of America

QR

Escanee el código QR para guardar los datos de contacto como tarjeta de visita electrónica (TVE) en su teléfono smartphone

¿Eres de otra región o tienes preguntas sobre otros temas?