Temperature transmitter
ZT-F2 is a temperature transmitter for TRASY2 which is required for measuring winding temperature with TRASY2. It offers quick and easy configuration of gradients via DIP switches (thermal image of winding temperature) and comes with additional analog output (4...20 mA). Optional PT100 sensor possible.
Sus ventajas de un vistazo
-
Digital-ready: Integrated MODBUS RTU / RS485 interface
-
Redundant: Maximum availability through flexible signal transmission
-
User-friendly: Intuitive gradient adjustment via DIP switches (winding temperature)
-
Robust: Reliable operation under all environmental conditions
-
Retrofit-friendly: No extensive modifications in existing applications needed
-
Flexible: Fully compatible with all common thermometer pockets (EN 50216-4)
Información sobre el producto
| Operating temperature | -40...+80 °C |
| Ambient air temperature | -50...+85 °C |
| Corrosion protection class | C4H standard |
| Degree of protection | IP56 in accordance with DIN EN 60529 |
| Cable gland | 4 x M25 x 1.5 nickel-plated brass |
| Output/Interface | Up to 2 x for Pt100 / Pt1000 or up to 2 x 4...20 mA, others on request |
| Measuring range | Depends on thermometer used |
| Electric connection | 1 x M16 x 1.5 WADI / 2 x M25 x 1.5 WADI |
| Sensor gland | 1 x M16 x 1.5 WADI; 2 x M25 x 1.5 WADI |
| Cable glands | 1x M16 x 1.5 WADI; 2 x M25 x 1.5 WADI |
| Connection terminals | 4 mm2 single core |
| Ventilation | Via pressure compensation element |
| CT nominal current | 2 A from current transformer |
| Overload stability | Continuously max. 3 A (corresponds to 1.5 x CT nominal current), 12 A for 30 sec. |
| Gradient adjustment | Via dip-switch |
| Ambient temperature | -50 - 85° C |
| Location | Indoors and outdoors, tropical proof |
| Heating | Integrated in immersion tube |
| Rated insulation voltage | 300 VAC, 50 Hz |
| Analog output signal | Up to 2x for Pt100 / Pt1000 or up to 2x 4 - 20 mA, others on request |
| Current output | 4 - 20 mA |
| Power supply | min. 10 VDC - max. 30 VDC |
| Load | max. 750 Ω for 24 VDC |
Seleccionar idioma
| Operating temperature | -40...+80 °C |
| Ambient air temperature | -50...+85 °C |
| Corrosion protection class | C4H standard |
| Degree of protection | IP56 in accordance with DIN EN 60529 |
| Cable gland | 4 x M25 x 1.5 nickel-plated brass |
| Output/Interface | Up to 2 x for Pt100 / Pt1000 or up to 2 x 4...20 mA, others on request |
| Measuring range | Depends on thermometer used |
| Electric connection | 1 x M16 x 1.5 WADI / 2 x M25 x 1.5 WADI |
| Sensor gland | 1 x M16 x 1.5 WADI; 2 x M25 x 1.5 WADI |
| Cable glands | 1x M16 x 1.5 WADI; 2 x M25 x 1.5 WADI |
| Connection terminals | 4 mm2 single core |
| Ventilation | Via pressure compensation element |
| CT nominal current | 2 A from current transformer |
| Overload stability | Continuously max. 3 A (corresponds to 1.5 x CT nominal current), 12 A for 30 sec. |
| Gradient adjustment | Via dip-switch |
| Ambient temperature | -50 - 85° C |
| Location | Indoors and outdoors, tropical proof |
| Heating | Integrated in immersion tube |
| Rated insulation voltage | 300 VAC, 50 Hz |
| Analog output signal | Up to 2x for Pt100 / Pt1000 or up to 2x 4 - 20 mA, others on request |
| Current output | 4 - 20 mA |
| Power supply | min. 10 VDC - max. 30 VDC |
| Load | max. 750 Ω for 24 VDC |