MESSKO® MCTA-5
CT current simulator for testing and setting winding thermometers with thermal image
You can use the CT current simulator in the test field, during commissioning or during maintenance of CT-current-powered temperature measurements. It is designed for mobile use on a switched-off transformer. Operation is simple: The AC current is set using the control button and checked using a display. The AC current is kept constant regardless of load (max. two thermometers in series or max. 40 VA). Furthermore, the output frequency (50/60 Hz) can be preset.
Your Advantages at a Glance
-
Use in the test field, during commissioning or during maintenance
-
Compact design specifically for service purposes – easy to transport
-
Simple operation and high functional safety
-
Constant AC current (0–5 A controllable) up to 40 VA load
Product Information
| Protection class | IP22 in acc. with EN60529 |
| Ambient temperature | -20 - 50 °C |
| Supply voltage | 90 - 250 V AC, 2 A max. |
| Line frequency | 50 / 60 Hz switchable |
| Fuse | 2 A, slow-blow |
| Output current | 0 - 5 A AC, 50 / 60 Hz at pole terminals 4 mm |
| Adjustment | Precision potentiometer |
Select language
| Protection class | IP22 in acc. with EN60529 |
| Ambient temperature | -20 - 50 °C |
| Supply voltage | 90 - 250 V AC, 2 A max. |
| Line frequency | 50 / 60 Hz switchable |
| Fuse | 2 A, slow-blow |
| Output current | 0 - 5 A AC, 50 / 60 Hz at pole terminals 4 mm |
| Adjustment | Precision potentiometer |
Select language