MESSKO® MMK
Magnetic oil level indicators for transformers
The MESSKO® MMK magnetic oil level indicator shows the fill level, without needing a float located in the container. The magnetic level gauge can be easily attached to existing flange connections (retrofit) in accordance with DIN 42552. A measuring tube is flanged to the container as a replicate container. Inside, there is a cylindrical float with installed permanent magnet. The indicator rail with the magnetic flaps is on the outside of the measuring tube. Depending on the fill level, the float magnet ensures that the magnetic flaps in the indicator rail turn 180°.
Información sobre el producto
Material |
|
Measurement tube | Stainless steel 1.4571, 40 x 1 mm |
Float | BUNA N with fitted permanent magnet |
Display rail | Makrolon (polycarbonate), glass clear UV-resistant |
Characteristics |
|
Measurement medium | Mineral oil (alternative liquids on request) |
Measurement range | Arbitrary (max. 2 m) |
Measurement accuracy | +/- 2 display valves |
Operating data | Max. pressure up to 1 bar |
Density | Min. 0.7 g/cm3 |
Viscosity | Max. 150 cSt (1.5 x 10-4 m2/s) |
Operating temperature | -40 - 80 °C |
Connection | DIN 42 552 Form B |
Options | Limit value contacts 230 V AC/0.8 A/60 VA/40 W Remote measurement value transfer 4 ... 20 mA |
Seleccionar idioma
Instrucciones de uso
MESSKO® MMK
Versión:
02
de
MESSKO® MMK
Versión:
02
cs
MESSKO® MMK
Versión:
02
pl
MESSKO® MMK
Versión:
02
fr
MESSKO® MMK
Versión:
02
pt
MESSKO® MMK
Versión:
02
ko
MESSKO® MMK
Versión:
02
es
MESSKO® MMK
Versión:
02
ru
MESSKO® MMK
Versión:
02
it
MESSKO® MMK
Versión:
02
zh
MESSKO® MMK
Versión:
02
en
Seleccione una opción para ver las descargas adecuadas
Technical Data
Material |
|
Measurement tube | Stainless steel 1.4571, 40 x 1 mm |
Float | BUNA N with fitted permanent magnet |
Display rail | Makrolon (polycarbonate), glass clear UV-resistant |
Characteristics |
|
Measurement medium | Mineral oil (alternative liquids on request) |
Measurement range | Arbitrary (max. 2 m) |
Measurement accuracy | +/- 2 display valves |
Operating data | Max. pressure up to 1 bar |
Density | Min. 0.7 g/cm3 |
Viscosity | Max. 150 cSt (1.5 x 10-4 m2/s) |
Operating temperature | -40 - 80 °C |
Connection | DIN 42 552 Form B |
Options | Limit value contacts 230 V AC/0.8 A/60 VA/40 W Remote measurement value transfer 4 ... 20 mA |
Descargas
Seleccionar idioma
Instrucciones de uso
MESSKO® MMK
Versión:
02
de
MESSKO® MMK
Versión:
02
cs
MESSKO® MMK
Versión:
02
pl
MESSKO® MMK
Versión:
02
fr
MESSKO® MMK