Protective housing |
Outdoor design, IP 55 protection |
Gearing |
Transmission gear for hand crank operation, ratio 2:1, auxiliary gear for position indication and blocking of drive mechanism |
Max. applicable torque |
Approx. 90 Nm at the output shaft with 200 N applied to the hand crank handle |
Number of operating positions |
Max. 17 |
Number of hand crank revolutions per tap change |
8 |
Tap position indicator |
Dial behind inspection window |
Tap change progress indicator |
Display behind inspection window |
Safety devices |
Mechanical locking
Padlock; operation is only possible after the key has been turned (forced engagement)
Electrical locking
Cam-operated switch; tap-change operation after unlocking via operating lever Switching capacity: 24 … 250 V = 100 W AC/DC |
Housing dimensions |
420 x 434 x 199 mm (W x H x D) |
Weight |
Approx. 25 kg |
Temperature range |
–45 °C to +70 °C |