Transformer Control

Chemicals factory

Case study


Example:

Switchable filter circuits MV for chemicals factory

Function of the compensation system:

Reduction of the harmonic currents of the 12 and 24-pulse rectifiers of the chlorine electrolyser system
Maintaining a power factor of 0.95 and better – reduction of the reactive power in the gas turbines

Type of compensation system:

Switchable 30 kV 40 Mvar filter circuit system with special double-chamber switch and division for the 5th, 7th and 11th harmonics

Scope of the delivery

3 stations for the single filter and double filter (without baseplate), delivery of the components, installation including cooling system (redundant), commissioning and performance tests