Example:
Switchable filter circuits MV for chemicals factory
Function of the compensation system:
Reduction of the harmonic currents of the 12 and 24-pulse rectifiers of the chlorine electrolyser system
Maintaining a power factor of 0.95 and better – reduction of the reactive power in the gas turbines
Type of compensation system:
Switchable 30 kV 40 Mvar filter circuit system with special double-chamber switch and division for the 5th, 7th and 11th harmonics
Scope of the delivery
3 stations for the single filter and double filter (without baseplate), delivery of the components, installation including cooling system (redundant), commissioning and performance tests